By Carson Marsh
On August 13, 2026, the California Public Utilities Commission (CPUC) approved Resolution SED-13, which adopts an Administrative Consent Order between CPUC’s Safety and Enforcement Division (SED) and Pacific Gas and Electric Company (PG&E) concerning the 2022 Mosquito Fire. Under the agreement, PG&E will pay a $21 million fine to California’s General Fund and provide up to $1 million in shareholder funding for an independent review of its Transmission Centralized Inspection Review Team (CIRT). The settlement resolves SED’s enforcement investigation without a formal enforcement proceeding.
The Mosquito Fire began on September 6, 2022, near Oxbow Reservoir in Placer County. According to the incident report, the fire burned approximately 76,788 acres, destroyed 78 structures, damaged 13 other structures, and resulted in two reported injuries. The fire began near PG&E’s Oxbow Junction Pole, which connected three 60-kilovolt transmission circuits through two switches known as Switches 47 and 49. In its investigation, SED concluded that electrical arcing at the lowest jumper between the switches most likely created an ignition source for the fire. However, SED noted that it does not determine the official cause of fires and that the U.S. Forest Service led the fire investigation.
SED’s investigation identified several alleged violations of the CPUC’s General Order 95 (GO 95), which establishes safety requirements for overhead electric facilities. Rule 18 requires utilities to identify and correct safety hazards and establishes deadlines for certain repairs. In a Tier 3 High Fire-Threat District, utilities must correct certain conditions that present a fire risk within six months. SED alleged that PG&E failed to timely correct several maintenance issues near the fire area, including loose tie wires. SED also alleged that PG&E violated Rule 19, which requires utilities to cooperate with Commission investigations and preserve relevant evidence, when PG&E disposed of Pole 09/131 and attached equipment after SED instructed the utility to preserve them.
SED also alleged violations of Rule 31.1, which requires utilities to design, construct, and maintain their electrical systems to provide safe and adequate service and to follow accepted good practices where GO 95 does not provide a more specific requirement. According to SED, PG&E failed to complete required testing of Switches 47 and 49, failed to maintain vegetation clearance around the Oxbow Junction Pole, and cancelled six recommended repairs near the pole without adequate justification. SED’s investigation also found that Switch 47 had experienced operational problems before the fire, including a burned lower phase in April 2022 and several unsuccessful attempts to remotely operate the switch later that month.
SED separately investigated whether PG&E maintained sufficient clearance between the electrical equipment and the Oxbow Junction Pole. GO 95 Rule 37 and 54.4 establish minimum clearance requirements for electrical conductors. SED concluded that PG&E failed to maintain the required clearance between the Oxbow Junction Pole and the lower jumper connecting Switches 47 and 49, creating an electrical fault path. Investigators observed that the lower jumper bent toward the pole and documented contact or near-contact with the switch control rod, along with evidence of scorching. SED concluded that the lack of clearance resulted in electrical arcing and that the arcing most likely created an ignition source for the fire.
The settlement does not require PG&E to admit every violation SED identified during its investigation. Instead, the Administrative Consent Order resolves the disputed investigation while imposing both a monetary penalty and additional corrective measures. As part of the settlement, PG&E will provide up to $1 million in shareholder funding for an independent review of CIRT, the PG&E team responsible for reviewing certain inspection findings and recommended repairs. The review will examine CIRT’s policies and procedures, effectiveness, documentation, and compliance with GO 95 and recommend potential improvements. SED may pursue additional enforcement related to CIRT after reviewing the results.